Reverse Power Relays
WILMARProtective Relays 700 Series w/ Adjustable Time Delay
TERMINAL STRIPS
#6 - 32 SCREWS
Function: 32
ANSI/IEEE C37.90-1978
UL file No. E58048
CSA file No. LR61158
Several types of Reverse Power Relays are available
including relays sensitive to reverse reactive power
(KVAR). WILMAR is the leading brand of reverse power
relays. Our rugged sealed construction provides con-
tinuous and reliable operation unaffected by shock,
vibration or other severe environments. Reverse Power
Relays are used for the protection of generator sets
operating in parallel.
3.0
Model 710TD
3 7 /8
4 5 /8
13/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Designed for 120, 220 or 266 volt
line to neutral connection
PART NUMBER SELECTION
Model 720TD (X) thru 724TD (X)
PRODUCT SPECIFICATIONS
Part Number
Line Voltage ......................................
700TD Series
Model 710TD = 120 V, 220 V or 266 V, line to neutral
Model 730TD = 120 V, 230 V, 380 V, 460 V, L-L, 3
Phase or 120 V, Single Phase, L-N
All models for three phase, three wire sensing are
available, see part number selection
For operation on three phase,
three wire
PART NUMBER SELECTION
Line Frequency ................................. 50-500 Hz.
Sample Part No.
720TDX
Current Requirements ..................... 0 to 5 amp max direct or from CT with 5 amp
secondary
Type:
710TD = 120V, 220V, 266V line to neutral
720TD = 120V, L-L, 3 Phase
Trip Adjustment ............................... Screwdriver adjustable 4% to 20% (of the 5 amp rating)
721TD = 230V, L-L, 3 Phase
722TD = 380V, L-L, 3 Phase
Time Delay Adjustment .................... 0.5 to 20 seconds, screwdriver adjustable
723TD = 460V, L-L, 3 Phase
724TD = 575V, L-L, 3 Phase
Output Contacts ............................... One set N.O., one set N.C.
Contact Ratings ................................ 5 amp resistive at 120 AC or 28 Vdc
725TD = 416V, L-L, 3 Phase
730TD = 120 V, 230 V, 380 V, 460 V, L-L, 3 Phase or
120 V, Single Phase, L-N
Power Consumption ........................ Voltage circuit: 2 VA max.
Current circuit: 4 VA max.
Mounting:
X = Flange
Blank - Stud
Notes:
Options:
1. Remove screw for access to the pick-up and time delay adjustments.
2. Clockwise rotation of the pick-up adjustment will raise the reverse trip point.
7 = Reverse Inductive, 60 Hz
3. Clockwise rotation of the time adjustment will increase the time delay.
4. Polarity of the voltage and the current connections must be observed for true power sensing.
Consult factory for additional models.
5. Interchanging connections on terminals 5 and 6, will cause the output contacts to pick-up on forward power and dropout on no power or reverse power.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)