datasheetbank_Logo
Integrated circuits, Transistor, Semiconductors Search and Datasheet PDF Download Site

AD1072F View Datasheet(PDF) - MicroPower Direct, LLC

Part Name
Description
View to exact match
AD1072F Datasheet PDF : 2 Pages
1 2
AD1072F Series
Very Low Cost, 72W
DIN Rail Mount
Single Output
AC/DC Power Supplies
New Industrial
Key Features:
72W Output Power
DIN Rail Mountable
Universal AC Input
UL 508 Compliant
EN60950 Compliant
12, 24 & 48 VDC Outputs
Cond./Rad. EMI Class B
>150 kH MTBF
Supplies!!
Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Input
Parameter
Conditions
Min. Typ. Max. Units
Input Voltage Range
Universal 100
127
240
VAC
370
VDC
Input Frequency
47
63
Hz
Inrush Current, Cold Start
110 VAC
22
A
220 VAC
44
A
LOW COST!
Leakage Current
264 VAC
1.8
mA
Output
Parameter
Conditions
Min. Typ. Max. Units
Output Voltage Accuracy
±0.5
%
Output Voltage Adjustment Range
±10.0
%
Line Regulation
Vin = Min to Max
±1.0
%
Load Regulation (Note 1)
Iout = 20% to 100%
±1.0
%
Hold Time
110 VAC, Full Load
10
220 VAC, Full Load
20
mSec
Ripple & Noise (20 MHz) (Note 2)
See Model Selection Guide
Output Power Protection
Power Limit 130
160
%
Transient Recovery Time (Note 3)
RoHS Compliant Transient Response Deviation
50% Load Change
2
5
mS
%
Temperature Coefficient
±0.04 ±0.05 %/ºC
Output Short Circuit
Models available General
Continuous With Autorecovery
to 360W! Call Parameter
Conditions
Min. Typ. Max.
Input - Output 3,000
Units
today for details Isolation Voltage
Input - FG (Frame Ground) 2,000
VAC
Output - FG (Frame Ground) 500
MicroPower Direct
292 Page Street
Suite D
Stoughton, MA 02072
USA
Isolation Resistance (Note 4)
Switching Frequency
Environmental
Parameter
Operating Temperature Range
Storage Temperature Range
500 VDC 100
Fixed
80
Conditions
Min. Typ. Max.
Ambient -20 +25 +50
-20
+85
MΩ
kHz
Units
ºC
ºC
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
W: www.micropowerdirect.com
Cooling
Humidity
Vibration
Physical
Free Air Convection
RH, Non-condensing
95
%
10 Hz ~ 2 kHz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
Case Size
4.76 x 4.33 x 2.2 Inches (121.0 x 110.0 x 56.0 mm)
Case Material
Aluminum (Base) and Steel (Cover)
Connection
Screw Terminal
Reliability Specifications
Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25ºC, Gnd Benign 150
kHours
Safety Standards
UL 1950, EN 60950, IEC 60950
EMI Compliance
Compliance to EN55011, EN55022 (CISPR22) Class B
EMS Immunity Compliance
EN6100-4-2,3,4,5,6,8,11 Level 3
 