Only One Name Means ProTek’Tion™
low profile 240v ac power line surge suppressor
587B062LPE - 587B302LPE
Description
The 587B Low Profile (LPE) Series is designed for European applications where no line to ground or neutral to ground
suppression is allowed. These modules employ a three stage technology proven to be the most cost effective and reli-
able method in protecting sensitive electronic equipment from over voltage transients.
This series is designed to protect AC powered equipment from the 6,000 Volt peak open circuit voltage and 3,000 Amp
short circuit current as defined in ANSI/IEEE C62.41, Category CI.
low profile
Features
The 587BxxxLPE Series offers a high degree of protection against 240 VAC EMI line noise. It is ideal for protecting 800
Volt components because the solid state TVS technology assures that the line-to-neutral voltage will not exceed 800
Volts. While the modules are designed for transient voltage protection, the advanced circuitry will also attenuate the
amplitude and slow the rate of rise of high frequency noise acting as an EMI filter. The 587BxxxLPE Series includes
common mode protection, which are effective in reducing interference from line to equipment and are effective in
reducing equipment generated noise to meet FCC, VDE and CSA interference requirements.
applications
• Compatible with IEC 61000-4-5 (Surge): 1kA, 8/20µs, Level 4 (Line-
Gnd) & 333A, Level 4 (Line-Line)
• Meets ANSI/IEEE C62.41 Outdoor Requirements
• Listed to CSA, File LR65240 (Except 587B302LPE)
• Differential Mode Protection
• Low Clamping Voltage
• Nanosecond Response Time
• Long Life and Maintenance Free
• Finger Safe Connections
• Hard Wired Equipment AC Power Protection
• Load Side Distribution Systems
• Secondary Protection for Light Industrail AC Power
Mechanical characteristics
• Low Profile Plastic Package
• Approximate Weight: 360 grams
• Flammability Rating UL 94V-0
figure 1
transient voltage threat condition
8
6
figure 2
typical clamping action of a 15a module
6
4
4
2
2
0
0
0
10 20
30
40
50
60
t - Time - µs
0
10 20
30
40
50
60
t - Time - µs
Figures 1 and 2 are photographs of digitized waveforms showing the typical clamping action of a 15A module. A 12 Ohm resistor is used to repre-
sent a 10A equipment load. The load is then subjected to the ANSI/IEEE C62.41 Catagory CI test conditions (6000V/3000A). These photographes
contrast the effect on equipment with and without the protector.